1.0       3 phase Power System Simulator, Make Doble, Type: F6150. Quantity: 1 No.

Power System Simulator uses signal processing, power amplifier to simulate the operation of protective relays for various testing application. This Power System Simulator can check protection system and verifies protection settings by simulating system events.

This Power System Simulator tests all the protective relays covered under IEEE device Nos. This Power System Simulator is supported by very versatile and automatic protection softwares such as,

  • F6Test for pre-configured automated testing using templates for all protection schemes.

  • ProTest for fully customized automated testing software providing flexibility for testing of protection schemes

  • The F6000 Control Panel for quick manual style interactive testing.

This Simulator can also be used for calibration testing of transducers and metering application including the new standard 0.2 class metering system.

FOR MORE INFORMATION (www.doble.com/products/f6150.html)

2.0     T3000 : Sub-station Test System

This is a sub-station Maintenance and Commissioning test equipment Model T3000, Make ISA, Italy.  Quantity : 2 Nos.

It’s a Multi-Function system for testing substation equipment such as,

  • Current Transformers,

  • Voltage and Power Transformers,

  • All Type of Protection Relays,

  • Energy Meters and Transducers.

  • T3000 can carry out testing operations during commissioning and maintenance of substation.  

  • It carries out the test on relays of all types (voltage, current / power, frequency and df/dt) and of current and voltage transformers.  

T3000 has a powerful multi-meter and phase angle meter with oscilloscope functions.

FOR MORE INFORMATION (www.isatest.com/products/t3000.asp)

3.0     SECONDARY INJECTION TESTING KIT: Quantity  :  5 Nos.

This test set is suitable for testing and calibration of all types of relays including static, microprocessor based, electromechanical relays etc.

The rating of this set is,

3.1      0-100\250 Amp, distortion free alternating current.  Current can be selected in ranges of 1A, 5A, 10A, 25A, 50A & 100A\250A.

3.2        0-440V A.C., Voltage can be selected in range of 0 - 63.5V, 110V, 230V & 440V.

3.3        0-250V   D.C., 2A, Capacity, low ripple content D.C. source.

 

 4.0    PRIMARY INJECTION TEST SET:  Quantity   :  3 Nos.

This set is used for testing Ratio of current Transformer, bi-metal relays and primary circuit injection etc.  The set can inject maximum upto 1000A.  The range selection is 0-250A / 500A / 1000A.

 5.0    MEASURING (PHASE SHIFTING) RELAY TEST SET: Quantity : 4 Nos.

This set is suitable for testing relays with circular characteristics and relay with specified maximum torque angle.

        This set has,

5.1       Current source upto 10A.

5.2       Voltage source upto 110V.

5.3     Phase shifter with continuous adjustment of phase angle from 0 to 360 degree with phase angle meter.

 

 6.0    THREE PHASE CURRENT AND VOLTAGE INJECTION TEST SET :
        Quantity   :  1 No.

This set is used for simulation of motor starting condition and for three phase overall recalibration of motor protection relay, testing and calibration of energy meters, etc.

The rating of the set is,

6.1     Three phase current with individual control in steps of 1A, 5A, 10A, 25A and 50A.

6.2     Three phase voltage 110V A.C. Fix.

6.3     D.C. source 0 - 250V DC, 2Amp. 

 

7.0       HIGH VOLTAGE TESTING SET:  Quantity  :  2 Nos.      

         This set is used for High Voltage Testing of switchgears, cables, bus-bars etc.

         The rating of this set is,

7.1       0-70 KV D.C./ 10mAmp.

7.2       0-45 KV D.C./ 10mAmp.

 

8.0   FREQUENCY GENERATOR : Quantity : 3 Nos.      

This set is used as a highly stabilized variable frequency and voltage source for testing frequency relays. A facility for testing rate of change of frequency feature as well as third harmonic injection for 100% Stator Earth Fault Protection Check.

9.0       C.T. KNEE POINT VOLTAGE CHECK TEST SET:  Quantity  :  1 No  .      

This set is specifically designed for testing of saturation characteristics of CTs having very high-knee point voltage.

The rating of set is,

9.1       0-500V, 5A.

9.2       0-2000V, 1A. 

 

10.0   OIL TEST SET:  Quantity :  1 No.

        This  set  is  utilized for testing dielectric strength of insulating oil.

         The rating of the set is,

10.1        This set is motorized.

10.2        Maximum output voltage is 0-60 kV. 

 

11.0   TURNS RATIO TEST SET:  Quantity  :  1 No.                    

This set is used for checking turns ratio of power transformer (1 Phase & 3 Phase).  The range of turns ratio is from 1-111

12.0   DIGITAL LOW RESISTANCE MICRO - OHM METER: Quantity  : 6 Nos.

This unit is designed on the principle of Kelvin's bridge method.

This unit has high accuracy of 0.1% and is used for measuring winding resistance   of Alternator, Transformer, H. T. Motor, Current Transformer secondary winding, circuit breaker power contact resistance etc.

This unit gives fast and stable readings for High Power (300 MVA), High voltage or high current transformers. It is suitable for Live Switchyard. Direct read out feature of resistance on 4 ˝ digit LCD display with back light is available. It is totally protected against inductive load and surges works on 230 V AC mains. It has high stability, high voltage compliance and extremely low ripple source.

13.0   DIGITAL TIME INTERVAL METER :  Quantity :  4 Nos.

This is a digital display time interval meter with accuracy of 0.1% and measurement from 1 mSec. to 999.9 Sec.

14.0   CIRCUIT BREAKER OPERATING TIME INTERVAL METER: Quantity : 2 Nos.

High accuracy Digital micro processor based instrument for measurement of circuit breaker closing and tripping time simultaneously for

all the three poles. This unit has digital display. It can measure time from 1 m Sec to 999 m Sec. A useful instrument for checking circuit

breaker pole discrepancy and faulty operating mechanism.

15.0    ACCESSORIES : MINIMUM 4 SETS.

The following testing accessories are used along with the major testing equipments.

15.1  5000V Motorised Megger Battery Operated:

       These meggers are used for measurement of insulation resistance and polarization index of HT equipments.

 

15.2  500V/1000V/2500V/5000V Digital Megger :

These meggers are used for testing, I.R. value, polarization index and step voltage test of HT equipment.

This instrument gives a direct value of polarization index.

15.3   D.C.Source Box :

This source box output is ripple free, non-distorted output of capacity 0‑230 Volts and 2 Amp/10 Amp.

15.4  Polarity Test Box :

Specifically designed for checking polarity of current and potential transformers.

15.5    Three point method digital earth resistance testing kit.

 

15.6    AC Ampere Leakage Current Meter :

         This is a sensitive meter capable of measuring currents as low as 2 mA.

 

15.7     Three Phase Variac :

This instrument provides a three phase continuously variable voltage supply from 0-470V, 10 Amp.

15.8      AVO meters of high accuracy. 

15.9      Hand Driven Megger of 500V and 1000V.      

15.10    Precision Class AC Ammeters.        

15.11    Digital Multimeters of  very  high accuracy (Make : Fluke, Type :Fluke 175).   

15.12    Digital phase angle meter for measurement of phase angles from (+ 0o to +  180o).

 

16.0   PHASING ROD:  1 SET

A set of live phasing rod to identify the phasing out between the two supplies.  The range of phasing rod is from 2kV to 33kV.

The electrical measuring instruments used by  us  are calibrated with  reference standards traceable to  NPL, Delhi through  Electronics  Regional  Testing  Laboratory,  STQC  Department of Electronics.

117.0  POWER QUALITY ANALYSER :  Quantity :  1 No

This measuring equipment designed and manufactured by “FLUKE” measures / records continuously for 24 hours :

a)      Volts / Amps / Hertz

b)       Power :  KW, KVA, KVAR

c)       Harmonics for Voltage, Amps, Watts

d)       Sags, Swells recording of Voltage and Current

e)       Transients

 f)       Inrush current measurement

Above measurements are supported by sophisticated software

118.0  ENERGY STANDARDS – METER TESTING SYSTEM : Quantity:1 No.

These metering system measures and is supported by relevant software:

a)    3 Phase current, voltage, power factor and frequency

b)    3 Phase kW, kVAR & kVA and single phase kW, kVAR & kVA

c)    Energy : 3 Phase kWh, kVARh & kVAh

d)    Recording of kWh Energy for a period

Top