CONDITION MONITORING & DIAGNOSTIC TESTING OF
                                     


Back


     POWER TRANSFORMERS AND OIL (> 5 MVA)
      RECOMMENDED TEST AS PER IEC

  Winding

  • Insulation Resistance and Polarization Index Measurement at recommended test voltage.

  • Capacitance and Tan delta Measurement at 10 kV or Uo Voltage whichever is less.

  • SFRA (Sweep Frequency Response Analysis) Test.

  • Magnetic Balance test.

  • Turns Ratio Measurement for all taps at 10 kV or Uo Voltage whichever is less.

  • Excitation Current Measurement at 10 kV or Uo Voltage whichever is less.

  • % Impedance Measurement.

  • DC Winding Resistance Measurement at 1A /10A DC constant source.

  • Vector Group. 

  Bushing

  • Insulation Resistance Measurement at recommended test voltage.

  • Capacitance & Tan delta Measurement.

          - C1 Insulation at 10 kV or Uo Voltage whichever is less.

          - C2 Insulation at 0.5 kV or 1 kV.

  Insulating Oil

  • Visual Inspection

  • Oil Tan delta Measurement 

  • Oil Dielectric constant Measurement

  • Oil Resistivity Measurement