CONDITION MONITORING & DIAGNOSTIC TESTING OF    
                                  

Back


 

      H.T. MOTORS (3.3 kV to 11 kV and >250 kW)

 

      RECOMMENDED TESTS AS PER IEC

 

 

 

§       Tests on Stator

·    Insulation Resistance and Polarization Index Measurement at recommended test voltage.

·    Capacitance and Tan delta Measurement at 10 kV or Uo Voltage whichever is less.

·    Partial Discharge Measurement at 10 kV or Uo Voltage whichever is less.

·    DC Leakage current Measurement  (Hi-Pot test).

·    DC Winding Resistance Measurement at 1A /10A DC constant source.